Individual Metered
EI3-B24V
Certifications
Compliance
Outlet Type
24×
ELGO Combo Max 5-in-1
Plug Type
IEC 60309 (3P+N+E), 440VAC 6 hr IP44Product description
Individual Metered iPDU, 32A, 3P, 24 Outlet: ELGO Combo Max 5 in 1 connectors (C13/C15/C15A/C19/C21) - 24 Nos , 1.77" LCD display, 6 X 16A Hymag CB, Branch/Circuit level monitoring, SNMP V1, V2, V3, HTTPs, FTP, MODBUS RTU, MODBUS TCP, SMTP, Syslog, Redfish API, JSON RPC, RADIUS, LDAP, TACACS+, Dual Ethernet Ports - 10/100/1000 Mbps & 10/100 Mbps, TLS 1.2, CB Trip Detection, Daisy chaining upto 16 Nos , Electrical log feature, 1 10 AWG 5C, 3-meter power cable with Industrial Plug with 45 Degree Angled cable entry, UL, TUV, CE, RoHS, Aluminum chassis, Vertical iPDU.
Specifications
Input
- Nominal Voltage
- 415 VAC
- Rated Voltage
- 380-440 VAC
- Frequency
- 50 Hz / 60 Hz
- Input Plug
- 3Φ, 30A/32A, IEC 60309 (3P+N+E), 440VAC, 6hr, IP44
- Cord Length
- 3 meters, 45° Angled
- Input Current
- 32 A
- Power Rating
- 21 kVA at 380 VAC, 24 kVA at 440 VAC
Output
- Nominal Voltage
- 230 VAC / phase
- Rated Voltage
- 200-250 VAC / phase
- Frequency
- 50 Hz / 60 Hz
- Receptacles Configuration
- ELGO Combo Max 5-in-1, 24 Nos (C13 / C15 / C15A / C19 / C21)
- Over Current Protection
- Six (6) × 16A Hydraulic Magnetic Circuit Breakers, 10kAIC
Features
Input and Outlet MonitoringVoltage (V), Current (I), Apparent Energy (kVAh), Reactive Energy (kVARh), Active Energy (kWh), Power factor, Apparent Power (kVA), Reactive Power (kVAR), Active Power (kW), Frequency (Hz)
Outlet MeteringProvides independent outlet-level monitoring of electrical parameters for precise load analysis and efficient power management.
Power Measurements Compliant with ANSI C12.1 and IEC 62053- 21 conforms to CLASS 1 metering accuracy
User Interface1.77-inch TFT colour LCD for local status and measurement display.
A secure and responsive web-based user interface provides real-time power and environmental monitoring, alarm notifications, and access to historical logs from any standard web browser. Seamless integration with DCIM systems is supported via SNMP and Modbus TCP protocols
Protocol SupportHTTP(s), SNMP v1, v2c, v3, MODBUS TCP, SFTP, DHCP, IPV4, IPV6 Support, Telnet (CLI), NTP, SMTP, SSH, Redfish API, Syslog, LDAP, RADIUS, TACACS+, TLS 1.3
NetworkingPrimary Gigabit Ethernet (10/100/1000) port with secondary redundant 10/100 Ethernet port
CascadingSupport cascading of 16 iPDUs/controllers for centralized monitoring and management via a single network connection. Cascading reduces network port usage and simplifies installation while ensuring reliable data communication between master and slave units
Threshold SettingUsers can configure threshold limits for low load, near-overload, and overload conditions for input current at phase level.
Thresholds can also be defined for lower and upper limits of temperature and humidity sensors.
Visual indication is provided via front-panel LEDs, along with an optional audible buzzer alarm.
Notification & AlertsComprehensive alerts delivered over SMTP (email) and SNMP traps. Optional local audible/visual alarms ensure immediate awareness.
Real-time detection of circuit breaker trips with local alarms and remote notifications on current threshold exceedance
Configurable notifications for temperature/humidity exceedance, maintaining optimal rack conditions. Supports external sensors with warning/critical levels via SNMP/SMTP.
Instant alerts for door open/close, smoke detection, and water sensor via SNMP traps or email. Integrates with DCIM for automated responses
Firmware UpgradeSupports remote firmware upgrades over HTTPS with dual LAN ports for zero-downtime access. Local USB upgrades enable offline deployment in secure environments
Compatible SensorsTemperature, Humidity, Dew Point, Air Flow, Water Sensor, Smoke Detection and Door Position
Data loggingEmbedded non-volatile memory logs key metrics including voltage, current, power (kW/VA), energy (kWh), power factor, frequency, and events with timestamps.
Supports data export via CSV for analysis; retention up to 365 days or 1000+ records.
Outlet FeaturesElgo Series outlet/Receptacles combination of C13/C15/C15A/C19/C21 as per IEC 61984/ IEC 60320 and CE, TUV, UL, CSA certified.
E-lock provision for standard power cord locking.
Alternate Phase Receptacles per branch. (Black – Grey – White)
Environmental Requirements
- Maximum Operating Temperature
- 60 °C
- Relative Humidity
- 95 % RH non-condensing
Conformance
- Certification
- UL, cULus, TUV
- Compliance
- CE
- Environmental
- RoHS
- Standards
- IEC 62368-1
Mechanical
- Dimensions (H × W × D)
- —
- Weight
- —
- Toolless Mounting — Centre to Centre
- —
- Mounting Configuration
- Zero U / Vertical
- Shipping Dimensions
- —
- Shipping Weight
- —
- Material
- Aluminum
Ordering code
| Ordering code | Chassis Colour | Cable Entry |
|---|---|---|
| EIM-T630T-EE3YSVX | Black RAL-9005 | Top Feed |
| EIM-T630T-EE3YYVX | RAL PO Red colour | Top Feed |
| EIM-T630T-EE3YRVX | RAL Ultra Blue Colour | Bottom Feed |
| EIM-T630T-EE3YQVX | White RAL 9003 | Top Feed |